KTR5 electronic pressure switches actuate a relay once a preset
pressure value is reached and allow regulation of the hysteresis value.
Maximum preset pressure is adjusted by operating the right trimmer
located on the instrument, by rotating the screw clockwise to increase and
counter-clockwise to decrease.
Minimum preset pressure (hysteresis) is found analogously by operating
on the left trimmer of the instrument. The instrument, which is totally
solid state, has the relay adjustment separate from alimentation.
Technical Features:
Anodized aluminum body with AISI 316 stainless steel process fitting.
Can be connected to the system with a
1/4" BSP female threaded port or to a Cetop manifold without any
adaptors.
Installation position: It can be mounted in
any position.
Working temperature: from -20°C to +80°C
Switching frequency: 120 cycles/min.
Switching accuracy: 0,6% of set pressure
Switching pressure range: 0 - 100%
Adjustable hysteresis value: from 3% and 40%
of set value
Weight: 0.45 Kg.
Electric Features:
Power supply: 24V AC/DC w15%
Maximum contact load:
10A-24VDC
5A-250VAC
Electrical connection according to DIN 43650
Electrical protection according to
DIN 40050: IP65
We reserve the right to make construction modifications without prior
notice.
|
Type
|
Switching pressure range
|
Maximum pressure
|
|
KTR 50
|
0.2 > 2 Bar
|
7 Bar
|
|
KTR 51
|
1 > 10 Bar
|
25 Bar
|
|
KTR 53
|
3 > 50 Bar
|
120 Bar
|
|
KTR 54
|
5 > 100 Bar
|
250 Bar
|
|
KTR 55
|
10 > 200 Bar
|
500 Bar
|
|
KTR 59
|
20 > 400 Bar
|
600 Bar
|
|
KTR 59.6
|
40
> 600 Bar
|
800
Bar
|
|