TR5 pressure transducers give out a current
signal directly proportional to the value of the input pressure to which
they are connected.
Standards available signals are:
4-20 mA or 0-10Volts DC
Technical Features:
Anodized aluminum body with AISI 316 stainless
steel process fitting. It can be connected to the system with a 1/4"
BSP female threaded port or to a manifold with Cetop (NFPA) mounting
pattern without need of adaptors.
Installation position: it can be mounted in
any position.
Working temperature: from -20°C to +80°C
Non-linearity + hysteresis: < 0.2% of F.S.
Zero thermic drift: <2% F.S. from -10°C
a + 55°C
Weight: 0.3 Kg.
Electric Features:
Electrical connection according to DIN 43650
Electrical protection according to
DIN 40050: IP65
Electronic working temperature:
from -10°C to + 70°C.
Stocking temperature:
from -40°C to +90°C
External charge: 100 OHMS
Power Supply:
Signal 4-20mA 2 wires: from 12 to 30 VCC
Signal 4-20mA 4 wires: from 12 to 30 VCC/AC
Signal 0-10Volts 3 wires: from 12 to 30 VCC
Also Available for Vacuum Service:
Type: TRW5 with signal 4-20 mA 2 or 4 wires
at the following values:
-1bar=4mA, 0bar=12mA, +1bar=20mA
Type: TRW5N with signal 4-20 mA 2 wires at
the following values:
0bar= 4mA, -1bar=20mA
We reserve the right to make modifications to construction without
prior notice.
|
Type
|
Measuring interval
|
Maximum pressure
|
|
TR 50.1
|
0 > 2 Bar
|
7.5 Bar
|
|
TR 50
|
0 > 5 Bar
|
12 Bar
|
|
TR 51
|
0 > 10 Bar
|
25 Bar
|
|
TR 52
|
0 > 20 Bar
|
50 Bar
|
|
TR 53
|
0 > 50 Bar
|
120 Bar
|
|
TR 54
|
0 > 100 Bar
|
250 Bar
|
|
TR 55
|
0 > 200 Bar
|
500 Bar
|
|
TR 59
|
0 > 400 Bar
|
600 Bar
|
|
TR 59.6
|
0 > 600 Bar
|
800 Bar
|
|